Skip to main content

Harmonic Restraining in Differential Protection


The differential relay is used for protection of transformer ,alternator and large rating HT motor. The  differential protection scheme is  also known as a zone protection. The relay must trip in case of the fault in the winding of the transformer. If the fault is outside of the zone,the differential relay must remain inoperative.

The transformer draws a large current at the time of switching on of the transformer at no load. The large current drawn by the transformer is known as inrush current or magnetizing inrush current, The magnitude of the inrush current may be 8 to 10 times  or even larger than this. The magnitude and duration of inrush current depends on the instant of the AC waveform at which the transformer is switched on. The waveform of the transformer inrush current is as given below.


The secondary current is zero and the primary current is high at the time of charging of the transformer. This difference in current between primary and secondary may lead to operation of differential protection relay. Thus, it is not possible to charge the transformer. If the protection relay is bypassed the differential protection of the transformer will get defeated. Bypassing the differential protection relay is not the solution.

The transformer generates 2nd and 5th order harmonic current at the time of charging because of non linear B-H characteristics of magnetic flux. The magnetic flux in the core is not sinusoidal and transformer generates harmonics. The sensing of the harmonics and restraining the differential protection relay operation at the time of charging of the transformer is one of the solution. This requirement is fulfilled by harmonic restraining in differential protection of the transformer.

If we analyse the inrush current by Fourier series, it has 2nd and 5th order harmonics. The 2nd order harmonic is rich when transformer draws magnetizing current at the time of switching of transformer. The frequency of the 2nd order harmonics is 100 Hz. The differential relay has a 100 Hz filter circuit which measures the frequency and the magnitude of the 2nd order harmonic current in the differential current.

If the relay senses the current of 100 Hz frequency and if the current is more than the differential current setting of the relay, the relay will observe that the transformer is taking the inrush magnetizing current and the relay blocks its main tripping mechanism. 

The setting of the 2nd order harmonic restraining is kept at 20-25 %  of the differential relay setting. If the current is below the differential relay setting, the relay does not trip because the relay will observe it as a transformer charging phenomenon. If the harmonic restraining current is more than the differential relay setting, the relay will trip with differential protection fault.

During over fluxing of the transformer, the transformer current has predominant 5th order harmonic current. The differential protection relay will trip in case of the over fluxing. If the over fluxing happens for short period of time, the differential relay should not trip. Therefore, to prevent the operation of differential protection relay in case of the over fluxing, 5th order harmonic restraining is provided.

If the magnitude of the 5th order harmonic current is more than the the setting of the differential protection relay setting the relay will trip. If the magnitude of the 5th order harmonic current is less than the the setting of the differential protection relay setting the relay will not trip. The setting of the 5th order harmonic restraining is generally kept 20- 25 % of the differential relay setting.

The basic circuit of harmonic restraint relay is as given below.












Saturday, October 19, 2019

Single Phase Transformer and Applications of Single Phase Transformer

Transformer transforms voltage from one level to other level without changing the power and frequency. Transformer is  a static electrical equipment and it does not have any moving part. The transformer has a magnetic CRGO steel core and two copper winding, one act as a primary and other act as a secondary.The transformer losses are very less because there is no moving part in the transformer, thus transformer is a high efficiency equipment.The transformer functions on the principle of Faraday;s law of electromagnetic induction.


When AC voltage is applied to primary of a transformer, the counter emf is generated in the primary according to rate of change of current. The counter emf generated in the primary limits the current in the primary. The counter emf  is zero if the DC is applied to the primary and the transformer can't be operated with DC. The flux is generated in the primary when alternating voltage is fed. The flux travels through the magnetic core and the alternating flux gets linked to the secondary. The alternating flux induce AC voltage in the secondary.

The RMS value of the voltage induced in the winding depends on the frequency, number of turns and the flux. 

Ep = 4.44 Np fФm

Es = 4.44 Ns fФm

Where,

Ep     = Induced EMF in primary winding
ES     = Induced EMF in secondary winding
Np     = Number of turns in primary winding
Ns     =  Number of turns in the secondary winding
f        =  Frequency
Фm   =  Flux in the core

There are two type of transformer single phase transformer and three phase transformer. The working principle of the transformer is the same. The single phase or three phase transformer can be used a  step down or step up transformer.

The single phase transformer has core and winding as its main part. The winding has resistance and to keep the transformer copper loss down the winding material of  small resistance value is selected. The laminated core is used to keep the eddy current losses to minimum value. The thin lamination of thickness 0.25 to 0.5 mm is used and the laminated sheets are isolated from each other. The insulating varnish is used for this purpose.
The transformer 500 kVA and above are of generally oil filled type.The transformer oil is used in the transformer tank for the insulation and cooling purpose.

Application of Single phase Transformer

Single phase transformer is widely used in low voltage application.The single phase transformers are mostly used to step down the single phase supply 220 volts to lower voltage. The transformer is used for power supply to electronic equipment. The transformer is used in the AC/DC rectifier, electronic circuits etc.



Friday, October 18, 2019

Ideal Transformer

The transformer has two winding - primary and secondary winding. The winding has resistance and the reactance. The equivalent circuit of a practical transformer is as given below.

Image result for equivalent circuit of transformer

The resistance and reactance of the winding must be as minimum as possible to have low power losses. However, it is only imaginary that winding has zero resistance and reactance. 

Definition of an Ideal Transformer

An ideal transformer is a imaginary transformer which has ;

  • Zero Copper loss - Copper loss of an ideal transformer is zero because the winding resistance of the primary and the secondary is zero. This means that both the winding are pure inductive in nature.
  • Zero leakage flux - The leakage flux is  part of the main flux which does not link to secondary winding of the transformer. In an ideal transformer, it is assumed that the  entire flux produced in the primary gets linked to the secondary and thus the entire flux produced in the primary is fully utilized.
  • Zero Iron loss - It is assumed that an ideal transformer has a core of infinite permeability. An ideal transformer takes very less magnetizing current to set up flux in the core.
  • 100% Efficiency -  If a transformer fulfills above three criteria the losses- eddy current, hysteresis and copper loss is zero and the transformer delivers output power equal to the input power.However, this is hypothetical condition and transformer  or any equipment can;t be 100 % efficient.

Ideal Transformer Model

The equivalent circuit of an ideal transformer is as given below.



When voltage V1 applied to primary, the counter EMF(E1) induced across the primary which opposes the primary voltage. The counter ? lags the applied voltage by 180 electrical degree.




The transformer draws more current at the instant of switching on of the transformer because the back EMF induced in the primary is zero. The transformer draw magnetizing current to produce the counter EMF in the primary. The magnetizing current lags the applied voltage by 90 degree. This current is called the magnetizing current Iμ .




The alternating magnetizing current set up the alternating flux in the core and the flux produced is proportional to the magnitude of the magnetizing current and in the phase with the current. The flux produced in the primary gets linked to the secondary and induce Evoltage. The induced voltage  E2 in the secondary is equal to the output voltage  V2 of the secondary.




Tuesday, October 15, 2019

Shell Type Transformer

The transformer can be categorized into core type transformer and shell  type transformer depending on the construction of the magnetic core and arrangement of the winding of the transformer. In the shell type transformer the core encircles the winding. 

Core of Shell Type Transformer

The core of the shell type transformer is made from the E-I and E-E type laminated sheet.


The core of the single phase shell type transformer has three limbs.This arrangement increase the mechanical strength of the core and also the winding remain protected from the mechanical shock.


Winding of Shell Type Transformer

The HV and LV winding is wound around the central limb and the central limb carries the entire flux (Ф ) and the side limbs carries the half (Ф/2 )of the total flux(Ф ).That is why the cross section area of the central limb is two times of the cross section area of the side limbs.The arrangement of the winding in a shell type transformer around the central limb is as given below.




The magnetic flux flows through two closed magnetic path and therefore the losses gets reduced and the efficiency of the transformer improves. The shell type transformer gives more output as compared to similar core type transformer. The core also provides better mechanical support to winding and under short circuit condition the electromagnetic force developed has less effect on the winding.

The HV and the LV winding is wound around the central limb in the sandwich arrangement. The HV winding is sandwiched between LV winding.





The quantity of the conductor required for the shell type transformer is less because both the winding are wound on the central limb. However, the insulation requirement is more as compared to the core type transformer because HV and LV winding is wound alternatively on the same limb. The design of the shell type transformer is complex compared to the core type transformer.

In case of any defect in the inner winding of shell type transformer, all the outer winding need to be removed for repairing or rewinding.


Cooling of Shell Type Transformer

In case of core type transformer natural air cooling may be sufficient. However, the forced air or forced oil cooling is required in a shell type transformer because the winding is surrounded by yoke and limbs.

Applications of Shell Type Transformer


The shell type transformer is used for the low voltage applications and are generally used in low voltage power circuits and electronic circuits.The cost of the shell type transformer for low voltage applications is less because the square or rectangular cross section area core can be used.

Due to complexity of the construction, the shell type transformer requires special fabrication facilities which increase the cost of productio

Transformer Rating

The maximum current that transformer can deliver to loads as known as the current rating of the transformer. The voltage, maximum current delivery of the transformer and the product of the voltage and maximum current known as VA rating are engraved in the nameplate of the transformer.

Related image

The rating of the transformer is adversely affected with abnormal temperature rise caused by the losses. The no load losses increases with an increase in the frequency and or voltage and the copper loss increase if the load power factor is more lagging which demands more current from the transformer and the copper loss gets increased. The losses can be kept within the limit by maintaining the rated voltage ,frequency and load current. 

The losses cause temperature rise of the transformer and if transformer is operated above its rated safe temperature limit, the winding insulation is apt to fail. The temperature can be held within the safe limit by proper cooling.

The losses depends on the V and I. The rating of the transformer depends on the losses. The losses  are independent of the power factor that is why the rating of the transformer does not depend on the load and it depends on the V x I which is known as VA rating of the transformer. The designer designs the transformer taking into account the maximum VA rating of the transformer. The transformer is specified for apparent power rating- VA rating.

The transformer primary VA is equal to the secondary VA plus the losses in the transformer. If the losses increase, the secondary VA delivery will get affected because of the temperature rise of the transformer. Generally the losses of the transformer is negligible the primary VA is equal to the secondary VA.

The VA rating marked on the nameplate is applicable for both the winding and VA rating of both the winding of transformer is the same. For a 440/220 Volts, 100 KVA transformer, the primary winding VA is 100 kVA and the secondary winding kVA is also 100 kVA.


Comments

Popular posts from this blog

नेपालमा जातजाति

नेपालमा जातजाती नेपाली बृहत शब्दकोषका अनुसार वंशपरम्परा, धर्म, गुण, आकृति, वासस्थान आदिका आधारमा विभाजित मनुष्यको वर्गलाई जात भनिन्छ भने शारीरिक बनावट आकार, प्रकार गुण, स्वभाव आदिका आधारमा छुट्टीने वा चिनिने जातीय विभाग, समूह वा वर्गलाई जाति भनिन्छ । यस्ता जात जातिले आफ्नै विशेष प्रकारका धर्म, नियम, संस्कारको पालना गरेका हुन्छन् । सामान्यतया यस्ता जातजातिको छुट्टै भाषा, भेषभुषा हुन्छ । वैवाहिक सम्बन्ध एउटै जातजाति भित्र हुने गर्दछ । नेपालमा विभिन्न प्रकारका जातजातिहरूको बसोवास भएको छ । त्यसैले नेपाली समाजलाई वहुल समाजको रूपमा चिनिन्छ । नेपालमा भएका जातजातिहरूलाई ब्राह्मण, क्षेत्री, वैश्य र सुद्र गरी ४ भागमा वर्गीकरण गरेको छ  ।    आदिवासी/जनजाति  आदिबासी जनजाति उत्थान राष्ट्रिय प्रतिष्ठान ऐन, २०५८ अनुसार “आदिबासी जनजाति भन्नाले आफ्नो मातृभाषा र परम्परागत रीतिरिवाज, छुट्टै सांस्कृतिक पहिचान, सामाजिक संरचना र लिखित वा अलिखित इतिहास भएको अनुसूची बमोजिमको जाति वा समुदाय सम्झनु पर्दछ  ।” जनजातिका विशेषताहरूलाई बुँदागत रूपमा भन्दाः  • जसको छुट्टै आफ्नै सामूहिक सांस्कृतिक पहिचान छ  

महानगरपालिका ,उप-महानगरपालिका र नगरपालिका गठन हुन चाहिने आधारहरु :-

महानगरपालिका ,उप-महानगरपालिका र नगरपालिका गठन हुन चाहिने आधारहरु :- ===========¥¥============ 1.महानगरपालिका गठनका आधारः- + कम्तीमा 3 लाख जनसंख्या + कम्तीमा वार्षिक रु 40 करोड आम्दानी + विद्युत्,खानेपा नी, सञ्चारको उपयुक्त सुविधा + नगरको प्रमुख सडकका साथै अन्या शाखा सडकहरु समेत पक्की भएको हुनु पर्ने + स्वास्थ्य सेवा सम्बन्धी विशिष्ठ प्रकृतिको सेवाको उपलब्धता + अन्तराष्ट्रिय खेलकुद कार्यक्रम आयोजनाका लागि आवश्यक पूर्वाधारको उपलब्धता + उच्च शिक्षाका लागि विभिन्न विषयहरुमा पर्याप्त अवसरको उपलब्धता र कम्तीमा एउटा विश्वविद्यालयको गठन + उच्च थप पर्याप्त शहरी सुविधाको उपलब्धता 2. उप-महानगरपालिका गठनका आधारः- + कम्तीमा 1 लाख जनसंख्या +कम्तीमा रु 10 करोड रुपैयाँ वार्षिका आम्दानी + नगरका प्रमुख सडकहरु पक्की भैसकेको हुनुपर्ने + विद्युत्, खानेपानी र सञ्चारको उपयुक्त सुविधा + उच्च गुणस्तरीय शिक्षा तथा सेवाको सुविधाको उपलब्धता + राष्ट्रिय तथा अन्तराष्ट्रिय स्तरको खेलकुद कार्यक्रमको लागि सामान्य व्यवस्था + सार्वजानिक उद्यानहरु र नगर सभागृहको व्यवस्था + अन्य अत्यावश्यक

नेपालका कलाकृतिहरु

नेपालका कलाकृतिहरू   नेपाली कलालाई विशेषतः चार भागमा वर्गीकरण गरिएको पाइन्छ : वास्तुकला, चित्रकला, मूर्तिकला र काष्ठकला  ।   (क) वास्तुकला • वासस्थान सम्बन्धी कलालाई वास्तुकला भनिन्छ । प्यागोडा शैली (छाने शैली), शिखर शैली, चैत्य, मुगल, गुम्वज शैली आदि यसका प्रचलित नमुना हुन्  ।  • वास्तुशैली एवम् कलाको दृष्टिबाट नपोलका मन्दिरहरूलाइ निम्न तीन पक्रारमा विभाजन गरिएको पाइन्छ : → प्यागोडा शैली (छाने शैली)  → शिखर शैली  → मिश्रीत शैली    प्यागोडा शैली (छाने शैली)  मन्दिरको बीचको भागखोक्रो छाडी तहतह परेको छानाहरू बनाइ निर्माण गरिएका मन्दिरहरूलाई प्यागोडा शैली (छाने शैली) भनिन्छ । यस्ता मन्दिर प्राङ्गणमा कलात्मक वस्तुहरू हुन्छन् भने टुँडाल र तोरणको प्रयोग गरिएको हुन्छ । पशुपतिनाथ मन्दिर, चाँगुनारायण, न्यातपोल, भक्तपुर आदि प्यागोडा शैलीका मन्दिरहरू हुन्  ।    शिखर शैली सुलुत्त परेर माथि चुलिँदै गएका झलक्क हेर्दा शिखरजस्तो देखिने छाना नबनाईकन मन्दिर निर्माण गर्ने कार्यलाई वास्तुकलामा शिखर शैली भन्ने गरिन्छ । यस्ता मन्दिरहरूको शिखर उँभोतिर सानो हुँदै गएको हुन्छ भने