EMF Equation of Transformer | Turns Ratio of Transformer
EMF equation of the transformer is very important for understanding the working of the transformer.When sinusoidal voltage is applied to primary of the transformer it draws magnetizing current to set up flux in the core.
The flux set up in the core gets linked to the primary and secondary winding of the transformer. The alternating flux set up in the core when links to turns of the primary and secondary winding induces voltage called EMF. The EMF induced in the transformer winding depends on number of turns and rate of change of the flux. The EMF induced across the primary and secondary always opposes the applied voltage.
The flux set up in the core gets linked to the primary and secondary winding of the transformer. The alternating flux set up in the core when links to turns of the primary and secondary winding induces voltage called EMF. The EMF induced in the transformer winding depends on number of turns and rate of change of the flux. The EMF induced across the primary and secondary always opposes the applied voltage.
According to Faraday's law of electromagnetic induction, if the alternating flux links to a coil the voltage is induced in the coil.The voltage induced in the primary and the secondary winding of the transformer is as given below. The RMS value of secondary induced EMF and primary induced EMF can be calculated using Faraday's law of electromagnetic induction.
Ep = - Np x dФ/dt
Es = - Ns x dФ/dt
Where,
Ep = EMF induced in the primary
Es = EMF induced in the secondary
Np = Number of turns in the primary winding
Ns = Number of turns in the secondary winding
dФ/ dt = Rate of change of the flux in the core
The minus sign shows that the voltage induced in the primary and secondary opposes the applied voltage.
Derivation of EMF Equation Of Transformer :
The derivation of the EMF equation of the transformer can be derived by calculating the rate of change of the flux in the transformer core. The flux set up in the core is sinusoidal.
The flux in the core changes from + Фm to -Фm in 1/2f seconds.
The voltage induced in the primary is
Ep = - Np x dФ/dt ---------(1)
The flux induced in the primary is because of the sinusoidal voltage applied to primary so the flux also varies sinusoidal. The instantaneous value of the flux in the transformer is ;
Ф = Фm Sinwt -------------(2)
Putting value of flux in the equation (1)
Ep = - Np x d/dt(Фm Sinwt)
Ep = - Np x wФm Coswt
Coswt = Sin(wt- π/2)
Ep = - Np x wФm Sin(wt- π/2)
The maximum value of voltage induced in the primary is
Ep = - Np x wФm
Ep = - Np wФm
w = 2πf
Ep(max) = Np 2πfФm -----------(3)
The root mean square (RMS) value of the induced voltage in the primary
Ep(RMS) = Ep(Max)/√2 -------(4)
Putting the Ep(max) value in equation(4)
Ep(RMS) = Np 2πfФm/√2
Ep(RMS) = √2π Np fФm
Ep(RMS) = 4.44 Np fФm -------(5)
Similarly, the root mean square (RMS) value of the induced voltage in the secondary is ;
Es(RMS) = 4.44 Ns fФm -------(6)
The general EMF Equation of the transformer is;
E= 4.44 N fФm -----------(7)
Voltage Transformation Ratio of Transformer
The ratio of the secondary turns to primary turns is known as the voltage transformation ratio of the transformer and it is denoted by letter 'K'.
Dividing equation(6) by equation(5)
Es/Ep = 4.44 Ns fФm/ 4.44 Np fФm
ES/Ep = Ns/Np =K --------(7)
If the secondary turns are more than the primary turns, the secondary voltage will be higher than the primary voltage and the turns ratio(K) is greater than 1. The transformer having voltage transformation ratio more than 1 is called step up transformer.
If the voltage transformation ratio (K) is less than 1, the transformer is called step down transformer.
The magnetizing MMF is negligible when substantial current flows in the primary and secondary winding of the transformer. The total MMF of the primary and secondary MMF is equal to the magnetizing MMF. The transformer is a constant flux machine as long as voltage and frequency remains constant.
MMFprimary + MMFsecondary = MMFmagnetizing
When transformer is substantially loaded, the magnetizing MMF can be neglected.
MMFprimary + MMFsecondary = 0
Np x Ip + Ns x Is =0
Np x Ip = -Ns x Is
Es / Ep = Ip / Is = K
Es / Ep = Ns / Np =Ip / Is = K
The voltage transformation ratio equation (7) of transformer is true if the flux in the transformer core is constant. The flux in the transformer changes if the supply voltage and or frequency gets deviate from its designed value.
Transformer Turns Ratio
The ratio of primary(Np) to secondary turns(Ns) of the transformer is known as transformer turns ratio,or TTR. It is denoted by letter 'a'.
Np / Ns = a
Ns / Np = K
Np / Ns = 1/K
a = 1 / K
Es / Ep = Ns / Np =Ip / Is = K
Ep / ES = Np/ Ns = Is / Ip = 1/K
Ep / Es = Np / Ns = Is / Ip = a
Illustrative example on transformer EMF equation
A two-winding transformer has primary winding with 300 turns and secondary winding with 10 turns. The primary winding is connected to 3300 V supply system. Calculate-
K = Es/ Ep
The magnetizing MMF is negligible when substantial current flows in the primary and secondary winding of the transformer. The total MMF of the primary and secondary MMF is equal to the magnetizing MMF. The transformer is a constant flux machine as long as voltage and frequency remains constant.
MMFprimary + MMFsecondary = MMFmagnetizing
When transformer is substantially loaded, the magnetizing MMF can be neglected.
MMFprimary + MMFsecondary = 0
Np x Ip + Ns x Is =0
Np x Ip = -Ns x Is
Ip/Is = - Ns/Np ------(8)
The negative sign shows that the current in the primary and secondary winding are in opposite direction with respect to the magnetizing current.The minus sign can be dropped for calculation of transformer transformation ratio.
From equation (7) & (8)
Es / Ep = Ip / Is = K
Es / Ep = Ns / Np =Ip / Is = K
The voltage transformation ratio equation (7) of transformer is true if the flux in the transformer core is constant. The flux in the transformer changes if the supply voltage and or frequency gets deviate from its designed value.
Transformer Turns Ratio
The ratio of primary(Np) to secondary turns(Ns) of the transformer is known as transformer turns ratio,or TTR. It is denoted by letter 'a'.
Np / Ns = a
Ns / Np = K
Np / Ns = 1/K
a = 1 / K
Es / Ep = Ns / Np =Ip / Is = K
Ep / ES = Np/ Ns = Is / Ip = 1/K
Ep / Es = Np / Ns = Is / Ip = a
Illustrative example on transformer EMF equation
A two-winding transformer has primary winding with 300 turns and secondary winding with 10 turns. The primary winding is connected to 3300 V supply system. Calculate-
- What is secondary voltage at no load?
- What is primary current when the 100-amp load connected to secondary?
- What is the apparent power flowing in the primary and secondary circuit?
- What is the turns ratio and voltage transformation ratio of transformer?
First transformer law:
Ep/Es = Np/Ns
Es = (Ep x Ns) /NP
Es = (3300 x 10)/ 300
Es = 110 Volts
Second transformer law:
Ip/ Is = Ns/Np
Ip = (Ns x Is)/ Np
Ip = (10 x 100)/300
Ip = 1000/300
Ip = 3.33 Amps.
Apparent power in primary circuit = Ep x Ip
= 3300 x 3.33
= 10989 VA
Apparent power in secondary circuit = Es x Is
= 110 x 100
= 11000 VA
Transformer turns ratio(TTR)
a = Np/Ns
a = 300/10
a = Np/Ns
a = 300/10
a = 30
Transformer voltage transformation ratio
Transformer voltage transformation ratio
K = Es/ Ep
K = 110/3300
K = 0.0333